Multi-line 2 CGC 400 Application Software series 1.x.

Multi-line 2 CGC 400 Application Software series 1.x.

You have chosen to download our software.

Within a few seconds, you will receive an email containing a download link.

Having trouble using the software? Please contact support@deif.com. 

Best regards, 

DEIF A/S

The software is subject to copyright DEIF A/S
By following the above mentioned link and downloading the file you automatically accept DEIF A/S copyright and license agreement (EULA). The license agreement can be found on www.deif.com/software

1.15.1

Corrections:

  •    Invalid SPN messages are no longer shown in the DM1 log. TSC1 SA is now configurable for the Perkins protocol.

1-15-2

29/06/2020

Version 1.15.2 based on version 1.15.1

Corrections:

  •    The MB will no longer trip on startup if the breaker is configured as a normally closed relay and the mains is okay.

1.15.1

26/02/2020

Corrections:

  •    Invalid SPN messages are no longer shown in the DM1 log. TSC1 SA is now configurable for the Perkins protocol.

1.15.0

24/01/2019

New features:

  • Support for LCD module based on the NT7538 display controller.

1.14.1

04/01/2018

Changes:

  • Improved precision of display readout of total energy counter.
  • Added new view line for absolute running hour counter with minutes.

Corrections:

  • Multi-input HW limit erroneous warning at power on.
  • EIC measurement alarms are now inhibited during EIC communication failure.

 

1.14.0

15/08/2017

Version 1.14.0 based on version 1.13.1

New features:

  • Phase sequence error is now detected and handled at both sides of the breakers (common alarm extended to two separate alarms in menu 2150).

Changes:

  • Phase sequence error is no longer detected when the voltage or frequency is outside volt./ frequency ok values.

Corrections:

  • Support of checksum in TSC1 telegram added for Volvo Penta EMS 2. Merge from SIPC 0497.
  • Phase sequence error status texts could appear even if they should be inhibited. GB would not close because of phase sequence error even if it was inhibited.

 

1.13.1

19/05/2016

Corrections:

  • Initiated cool-down cannot be aborted when a wire break fail class alarm is present.
  • Running hours offset is now stored and handled correct.
  • Scania EMS2 KWP2000 log clearing now possible.
  • Inhibit evaluation added to a number of AC alarms.
  • Genset data (e.g. oil pressure) was not displayed/updated correctly in the USW.
  • Negative values in range -1.0 to 0.0 showed correctly in the display.
  • Corrected "Limits relay" handling when setting up alarm output.
  • A problem with downloading new language from the USW has been corrected. The Language download returned “burn error”.

1.13.0

24/02/2015

Changes:

  • Scaling range 1 kV - 75 kV changed to 0.4 kV - 75 kV.

Corrections:

  • Attempting to stop during idle at start would ramp the engine to full speed and keep running, if the running detection speed had been reached during idle run
    Running hours counter not saved, and total energy counter not shown correctly in display
  • Space padding in master texts has been removed. Further when writing translations, space padding is removed from each text programmed 

1.12.0

27/11/2014

New features:

  • MTU ADEC CANopen engine communication interface now supports shutdown override.

Changes:

  • Mains voltage failure limit changed from 80-100 % to 40-100 %

Corrections:

  • Inverse Time Overcurrent protection aligned with IEC 60255 part 151 (AGC 200)
  • MTU MDEC 302/303 protocols battery voltage measurement corrected.
  • Regarding Idle start timer: Timer now resets if the Start Off timer is running.
  • AMF sequence was incorrect in some cases.
  • Start enable has to be energised to activate the regulation.
  • Option H5/H7, MTU alarm "AL Speed Demand Failure" no longer present all the time.
  • The reactive power was wrong when the phase rotation was L1L3L2.
  • Unit could reboot if a Modbus command was sent while 'Inhibit modbus commands' was active

1.10.0

08/04/2014

Changes:

  • Language translation changed. From now on it is not possible to select a different font.
  • The two fonts are now merged, containing all previously used characters.
  • The new font contains some new characters. If any unsupported signs are written to the device the signs will appear as ' ' (space). USW 3.37.0 or higher required.

Corrections:

  • Several menu texts were not using translations - Corrected.
  • Parameter outputs A and B could not be configured as "Limits" - Corrected.
  • Option C2 inverse over-current malfunctions when using "Customer" defined curve - Corrected.
  • The Fuel Pump Logic feature now disabled under power up while measurements are invalid.
  • Relay setting error could occur each time the unit starts up - Corrected

1.01.0

26/11/2013

New features:

  • RPM based on calculation from the AC reading

Corrections:

  • Pre-configuration of RMI 6-8 corrected

On this page, you can download software updates for your product(s) and help yourself to various utility tools and add-ons that will assist you in setting up, detecting faults and configuring your product(s).

Please be advised that not all of our products can be updated by the user. Nor do all of our products come with a utility tool. Consequently, the list on this page cannot be considered an overview of our product programme.

DEIF will register your download along with the used e-mail address for the purpose of sending out information on future updates, if requested.

DEIF cannot be made responsible for any consequences of failed product updates or use of utility tools. Nor can DEIF A/S be made responsible for consequences of changes in behaviour of products due to a software upgrade. It is always the responsibility of the user to ensure correct set-up and configuration before commissioning. Please study the version log of the software before updating the product.

Licence agreement for software downloaded from www.deif.com

Downloaded software remains the property of DEIF. The software may not be distributed for commercial purposes, changed or reused in full or in part or sold to any third parties.

The latest versions for full functionality

As always, we recommend that you install our offered improvements to fully utilise your DEIF product.

All improved software can be downloaded at your convenience at www.deif.com under “Software”.

Should you have any questions or experience problems finding the relevant software for your product, please feel free to call DEIF A/S at +45 96149614 or your relevant local DEIF office. Alternatively, we are always ready to assist you, if you send an e-mail to support@deif.com.