You’re about to download 1.07.0

The main changes implemented since the last version are as follows:

PM compatibility: 1.24.1.

New features:

  • Multiple busbars on CANshare is implemented, and 64 BTBs are available.
  • Remote display functionality is added. This includes a new controller type.
  • Reverse power: 3 AC protections are added.
  • Support of Perkins Stage V EIC protocol is added.

Changes:

  • MAINS connection are now allowed in the STAND ALONE variant and none GB or external GB.
  • DG HYBRID: PV semi start/stop commands are added to M-Logic and to the Modbus commands.
  • Weichai gas EIC protocol is updated with new data readings.

Corrections:

  • "Fuel optimization" and "Fuel optimization + running hours" are now working with percent values.
  • EIC transmission rate stability is improved.
  • DG HYBRID: It is no longer possible for the unit to send negative P-ref set points to a PV inverter.
  • Power emulation for AGC 150 with Option S1 is now calculated and shown correctly.
  • DG HYBRID: Corrected an issue where Emulation PV was not able to start with PV protocol set to OFF.
  • DG HYBRID: Corrected an issue where Goodwe DT and MT protocols would show negative ACP at values above 32768 W.
Ver. Date Description

1.07.0

21/06/2021

PM compatibility: 1.24.1.

New features:

  • Multiple busbars on CANshare is implemented, and 64 BTBs are available.
  • Remote display functionality is added. This includes a new controller type.
  • Reverse power: 3 AC protections are added.
  • Support of Perkins Stage V EIC protocol is added.

Changes:

  • MAINS connection are now allowed in the STAND ALONE variant and none GB or external GB.
  • DG HYBRID: PV semi start/stop commands are added to M-Logic and to the Modbus commands.
  • Weichai gas EIC protocol is updated with new data readings.

Corrections:

  • "Fuel optimization" and "Fuel optimization + running hours" are now working with percent values.
  • EIC transmission rate stability is improved.
  • DG HYBRID: It is no longer possible for the unit to send negative P-ref set points to a PV inverter.
  • Power emulation for AGC 150 with Option S1 is now calculated and shown correctly.
  • DG HYBRID: Corrected an issue where Emulation PV was not able to start with PV protocol set to OFF.
  • DG HYBRID: Corrected an issue where Goodwe DT and MT protocols would show negative ACP at values above 32768 W.

1.06.1

06/05/2021

Version 1.06.1 based on 1.06.0.

PM compatibility: 1.23.0.

Corrections:

  • Limit events is added in M-Logic for Extended M-Logic Alarms.
  • DVC 550/D550 now works with the EIC protocol Volvo Penta EMS 2.4.

1.06.0

29/04/2021

PM compatibility: 1.23.0.

New features:

  • DG HYBRID: Added new parameter #17132 "Curtail threshold".
  • Added support for John Deere Stage V EIC protocol.
  • Added support for Isuzu EIC protocol.
  • Added new parameter #6176 "Not running delay". Can be used as a hysteresis if the running feedback unexpectedly falls under the running detection level.
  • Added support for Kohler EIC protocol.
  • Added support for FPT + Iveco Stage V EIC protocol.
  • Added four new M-Logic alarms with extended delay in menu 3620-3650.
  • Added Event log entry when the application setup changes.
  • DG HYBRID: Added monitoring tool for Modbus master communication within the service view under communication analysis.
  • Added new GOV and AVR step test in parameter group #2970.
  • DG HYBRID: Added support for Sungrow Logger 1000 PV protocol.
  • DG HYBRID: Added support for Growatt PV protocol.
  • Added keyswitch for Diesel engine.
  • Added new controller type 'Engine Drive'.
    • Added MPU and EIC speed as PID1 input.
    • Added EIC as PID1 output.
    • Added digital input functions to control PID1 output (Semi manual mode).
    • Added ramp functionality for PID1.
    • Added new shortcut menu (Engine shortcuts).
  • DG HYBRID: Added support of PV breaker.
  • EIC speed (SPN 190) and MPU speed added to delta alarms.

Changes:

  • Default views for DG are changed.
  • Engine I/F list is reorganized in alphabetical order.
  • Fuel pump logic is available for Stand-alone and Core software versions.
  • The SunSpec identifying information shown in the display is improved.
  • PV protocols are listed in alphabetic order in the display and the USW.
  • DG HYBRID: Added fallback timer for power limit on SunSpec (Parameter 17180).
  • Minimum timer for AC busbar alarms is decreased from 0.1 to 0.04 seconds.
  • Text is changed in the shortcut menu.
  • Engine emission system failure Tier4 icon now follows FMI levels and SPN3349 set to 7 for protocols with 10 ms transmission rate.

Corrections:

  • Menu 6231 for GB close delay is no longer available when the application is power management.
  • Corrected that strange texts sometimes were shown in the USW log.
  • "L-L and P total" view now shows the correct value.
  • Power factor set point on Modbus is now correctly initialized after power-up.
  • General improvements to the D550/DVC 550 integration module.
  • Ph-ph voltage will not saturate before the hardware limit is reached.
  • Correct behavior of dfdt is now ensured when the number of periods are set above 12.
  • The variable needed for angle check in Q dep U< alarm is updated.

1.05.4

06/04/2021

PM compatibility: 1.22.0.

Corrections:

  • HYBRID: When reconfiguration of the RS-485 ports, power cycle of the unit is no longer needed.
  • HYBRID: The unit is now able to automatically switch between Sunspec addresses (40000, 50000 and 0). If Sunspec initialization is not compatible, reinitialization starts in 20 seconds.

1.05.3

02/03/2021

PM compatibility: 1.22.0.

Corrections:

  • Secured mode now works when Fuel optimisation is in use.
  • Priority update now works when more than 16 gensets or more than 16 mains are present in a plant configuration.
  • PMS priority data is properly maintained internally in all genset controllers.
  • When digital input 50 is not used as feedback, it is no longer disturbing the check of breaker status.
  • Breaker feedbacks are properly updated on the I/O status and the I/O setup page.

1.05.2

06/01/2021

PM compatibility: 1.22.0.

Corrections:

  •  Support is added for Volvo engine with 60 Hz as primary speed when Volvo proprietary engine speed is used.
  •  Generator under-frequency and under-voltage alarms are now inhibited during idle run.

1.05.1

08/12/2020

PM compatibility: 1.22.0.

Corrections:

  •  AGC 150 Hybrid controller got stuck in Sunspec initialize, due to a previously unknown Modbus model in the ABB PVS175 PV inverter.
  •  Transmitting DVC 550/D550 parameters over the CAN was irregular. This is corrected.

1-05-0

30/11/2020

PM compatibility: 1.22.0.

New features:

  • Support for the new input configuration interface.
  • DVC 550 PT100 measurements in display and selection in delta alarms.
  • EIC start/stop as a parameter.
  • M-Logic to start DG and close/inhibit close GB in auto mode. M-Logic to inhibit TB close.
  • Scania EMS2 S8 Engine I/F.
  • Configurable spinning reserve request using parameter 8930, not supported in BTB applications.
  • Ground breaker to CORE package
  • Shutdown override as new inhibit.
  • Parameter to use nominal frequency or rpm as reference for EIC speed offset.
  • Support for Volvo Penta EMS2.4.
  • New combined views with electrical data.

Changes:

  • Configurable multi inputs and new DM1 telegrams for JCB LiveLink. 
  • Racked out breaker On/off displayed in log.
  • Minimum level of "Frequency detection level (6165)" changed from 20hz to 10hz. 

Corrections:

  • Ground relay routine improved:
          - There is now always an overlap when transferring ground relays between DGs.
          - The best DG to hold the ground relay now keeps it closed during de-load and transfer of the ground relay happens when the de-loading DG is ready to open its GB.
          - Older versions with ground relay enabled are no longer compatible going forward.
  • AGC 150 Read log freezes controller. 
  • Phase calculations are now properly performed and transmitted to the DVC 550 & D550 when changed through M-Logic.
  • AC configuration in the D550/DVC 550 is now controlled by the AGC.
  • When configured for split phase operation, the nominal voltage setpoint is now correctly calculated for the DVC 550/D550.
  • New parameter #7746 DAVR AC config is introduced. This helps fix situations where the DAVR is not able to follow the AC configuration of the AGC.
  • Configuring a mains standalone application with the CAN bus set to OFF in the application configuration prevented the MB from closing. This has been corrected.
  • If a DG was running with its GB open and ground relay closed, and a mains then connected to the busbar, the ground relay would open. This has been corrected.
  • Alternative engine speed control for Volvo protocols including counter and checksum is added. Can be enabled with the new parameter 15110.
  • LTO now works correctly when unit is STAND-ALONE (non-sync).
  • Multi input alarm level 2 Min/Max now updates correctly when output limits are changed from multi input configuration in USW.

1-04-2

22/09/2020

PM compatibility: 1.17.2.

Corrections:

  •    TEST type in StandAlone (option S1) is limited to SIMPLE TEST.
  •    Limit evaluation of multi-input 23 alarm for use in M-Logic is now working.
  •    Included CAN Start/Stop in the Hatz proprietary CM1 telegram.
  •    Current handling of TIER 4 icons for the Hatz protocol.
  •    Read Aftertreatment 1 Intake Gas telegram for the Hatz protocol.
  •    Necessary to force a regeneration until current feedback is received from ECU.
  •    Fuel optimization + running hours does not swap DG's at fixed load.

1-04-1

29/07/2020

Version 1.04.1 based on 1.04.0

PM compatibility: 1.17.2

Corrections:

  • Errors regarding powermanagement applications with PV, ASC and battery controller corrected.

1.03.1

14/05/2020

PM compatibility: 1.17.2.

Corrections:

  • Analog output limits for the transducer output are corrected.
  • Transducer input range is extended on multi inputs to support the setup of limits corrected in #1.
  • STOP button has always a lid on the genset when running German rule, V0108.

1.03.0

03/04/2020

PM compatibility: 1.17.2

New features:

  •    DVC 550 and D550 are now supported by the AGC.
  •    Configurable amount of units for triggering Fatal CAN Error alarm, added in menu 8800.

Changes:

  •    Emulated value for I>> alarms added.
  •    Easy Connect is no longer blocking DG start in single DG applications.

Corrections:

  •    In AMF situations where the mains had no TB, and #7065 mains fail ctrl was set to "Start engine" and the DGs had to connect through a BTB to supply the mains, the MB would not open as it did not have information about whether or not the DGs Hz/V OK timer had run out. And as the MB would not open the BTB would not close resulting in a deadlock. This has been corrected.
  •    TB power capacity overrule timer will now run if there is an active MB trip failclass or the MB cannot be closed.
  •    Ring bus applications: If BTBs were closed at and under application configuration, opening a BTB could cause a DG to start without a proper start signal.
  •    Fixed a situation where opening a semi BTB, in a plant with an active start signal, would cause a DG to briefly engange its start prepare relay.
  •    In a plant where all DGs are divided by open BTBs, if for example, DG1 is running and needs help from DG2, DG2 would start and close its breaker, then synchronize the BTB, and as the BTB would close, DG3 would briefly engange its start prepare relay. This has been fixed.
  •    PMS + ISLAND + SEMI + GUIDED MIMIC: Start/stop buttons LED visible when relevant on genset.

1.02.0

26/03/2020

PM compatibility: 1.17.0.

New features:

  •    Two new EIC aftertreatment alarms have been added: "High SOOT warning" and "High SOOT shutdown".

Changes:

  •    Vector jump, df/dt, positive busbar sequence and directional over-current are now available in CORE MAINS and CORE BTB.
  •    New TIER 4 icons for JCB EIC are added.

Corrections:

  •    Parameter handling could in special cases cause decimals to be handled incorrectly in the display menu. This is corrected.
  •    Problems with freeze and white screen are now prevented.
  •    Analogue values from CIO 308 are now shown correctly in view-lines.
  •    JUMP menu causing unwanted parameter change is corrected.
  •    JUMP menu freeze is now prevented.
  •    Overspeed 2 menu (4520) is now shown correctly.
  •    GUIDED mimic is corrected with external breaker, so GB ON/OFF buttons do not lit up.

1.01.0

19/12/2019

PM compatibility: 1.17.0.

New features:

  • EIC: JCB J1939 protocol is added.
  • EIC: DEF level shown on lower tiny line in measure views. 
  • Stand Alone (option S1) is implemented. Breaker selection is extended with 'No breaker' and 'External breaker'.
  • LED colors can now be changed. An option to select a different LED color behavior in parameter 6084.
  • Now it is possible to change the source address for PGN GC1 and CM1 independently of each other for all engine protocols.

Corrections:

  • BTB can now be part of a plant with CORE units.

1.00.3

22/10/2019

PM compatibility: 1.17.0

Corrections:

  • External BTB position feedbacks are now working again.
  • Phase sequence error alarms are now working 3W3 coupling.
  • Service timers can now be reset.
  • Translated texts for I/O texts in Service View are now shown correctly.

1.00.2

05/08/2019

Version 1.00.2 based on 1.00.1

PM compatibility: 1.17.0

Corrections:

  •    Deloading the TB is now properly handled in test mode when parameter #8273 "Deload TB back sync." is enabled
  •    Multi inputs could go into overflow when set to voltage type
  •    Internal analog outputs (52/55) now works correct when used with GP PID.
  •    Genset priority would update even though the user had not issued an update.
  •    If mains ATS is active, and TB is closed onto a healthy busbar, and the controller is powercycled, the TB no longer opens and closes on power up.
  •    When sending a stop command during idle start the idle relay is kept closed.
  •    Fixed situations where multi start would not work correctly in ISLAND and AMF applications.
  •    M-Logic flag "Run all available island DG's" starts all DG's when activated.
  •    Mimic for BTB and MAINS with External breaker updated, so the respective buttons (open/close) are not visible.
  •    Various parameters added to parameter tree
  •    Improved Easy Connect functionality:
          - Rapid menu changes prevented
          - Info text on removed units
          - Possibility to remove the other unit with pop-up when only 2 in plant
          - Better handling of fault situations (Appl. hazard or Duplicate CAN ID)
          - Removed units are no longer blocked from running
          - Faster indication of changes on the other units

1.00.0

30/04/2019

PM compatibility: 1.17.0

  • Initial release

On this page, you can download software updates for your product(s) and help yourself to various utility tools and add-ons that will assist you in setting up, detecting faults and configuring your product(s).

Please be advised that not all of our products can be updated by the user. Nor do all of our products come with a utility tool. Consequently, the list on this page cannot be considered an overview of our product programme.

DEIF will register your download along with the used e-mail address for the purpose of sending out information on future updates, if requested.

DEIF cannot be made responsible for any consequences of failed product updates or use of utility tools. Nor can DEIF A/S be made responsible for consequences of changes in behaviour of products due to a software upgrade. It is always the responsibility of the user to ensure correct set-up and configuration before commissioning. Please study the version log of the software before updating the product.

Licence agreement for software downloaded from www.deif.com

Downloaded software remains the property of DEIF. The software may not be distributed for commercial purposes, changed or reused in full or in part or sold to any third parties.

The latest versions for full functionality

As always, we recommend that you install our offered improvements to fully utilise your DEIF product.

All improved software can be downloaded at your convenience at www.deif.com under “Software”.

Should you have any questions or experience problems finding the relevant software for your product, please feel free to call DEIF A/S at +45 96149614 or your relevant local DEIF office. Alternatively, we are always ready to assist you, if you send an e-mail to support@deif.com.