iE 250 Application SW (Flexible application)
iE 250 Application SW (Flexible application)
You have chosen to download our software.
Within a few seconds, you will receive an email containing a download link.
Having trouble using the software? Please contact support@deif.com.
Best regards,
DEIF A/S
The software is subject to copyright DEIF A/S
By following the above mentioned link and downloading the file you automatically accept DEIF A/S copyright and license agreement (EULA). The license agreement can be found on www.deif.com/software
2.0.9.0
2.0.9.0 based on 2.0.8.1
New features
- Three pump logic routines can now be set up to control the pumping of a substance.
- Implement ECU diagnostic to enable run coil and ECU power while the engine is stopped.
- All configuration dependent values are now possible to use in the flexible Modbus.
Changes
- Modbus timeout increased from 10 sec to 100 sec on iE 250 and iE 350.
- Number of possible Modbus connections changed from 20 to 100 on iE 250 and iE 350.
- EIC: Volvo Penta EMS2.4: "Engine Override Control Mode" changed to "Speed control".
- EIC: Volvo Penta EMS2.4: TSC1 will not be transmitted if VP70 is used for regulation.
- Added write permission for "Priorities" when the controller is in emulation.
Corrections
- Fixed issue where changes made in the UI were not registered.
- Fixed issue where the "IO configuration" menu would show empty slots.
- Fixed issue where tree-structure menu groups could not be collapsed using touch.
- Fixed issue where iE 250 failed to start up without MIO module.
- Fixed issue where configuring a Modbus value to "true" made the value "255" instead of "1".
- Fixed issue where measurements from multiple ECUs were not shown in UI for e.g. configuring alarms.
- Fixed issue where display user could not clear DM2 logs.
- Fix issue where iE controller could not start without MIO module.
- Fixed issue with missing alarm icons.
- Fixed issue where user could enter parameter values outside of valid range.
- Fixed checksum and counter for VP70.
- Fixed issue where PIM2.1 DIO levels were inverted.
- Fixed issue where removing network cable would activate system NOK, IO service error and "temperature too high" alarms.
- Fixed issue where CODESYS user management files were not included in backup/restore.
- Fixed issue where linked outputs in CODESYS were hidden in the IO configuration.
- Fixed issue where PWM was not working on MIO2.1.
- Fixed issue where Genset was not deloading correctly when it was connected to mains.
- Fixed issue where BUS TIE breaker could not deload and open a ring connected busbar.
2.0.9.0 |
04/05/2025 |
2.0.9.0 based on 2.0.8.1New features
Changes
Corrections
|
2.0.8.1 |
10/02/2025 |
Corrections
Changes
|
2.0.8.0 |
17/01/2025 |
2.0.8.0 based on 2.0.6.0 New features
Changes
Corrections
|