1.31.0

  • USW version required: 3.62.0
  • TDU version required: 1.4.3.1

PM compatibility: 1.41.0

New features

  • STORAGE: Added possibility of remote start over Modbus for DSE 8xxx, 7xxx, 6xxx, 4xxx power meter protocol.
  • STORAGE: Added global/local start of external genset(s) in open PMS.
  • STORAGE: Added possibility of remote start over Modbus for DEIF Genset control power meter protocol.
  • STORAGE: Added Lanli Tech BMS protocol.
  • STORAGE: Added Sicon VSG ESS protocol.
  • EIC: Added many new SPN texts for DM1 log.
  • STORAGE: Added Sungrow LC300 protocol support.
  • EIC: Added support for Scania S6 Industrial.
  • STORAGE: Added SYL Golden Shield Liquid-cooled (SYL G. S. Liq) BMS protocol.
  • STORAGE: Added new parameter 8043 "PMS Isochr. Q ctrl" which enables off-grid reactive power regulation in a PMS Isochronous master setup.
  • STORAGE: Added two new M-Logic outputs for skipping P ramp up and another for P ramp down.
  • STORAGE: Added three new parameters for following or skipping ramps.
    • Isochronous load share parameter: When the controller is isomaster and another storage controller is on the busbar it will no longer skip ramp if iso load share parameter is enabled.
    • Over-frequency and under-frequency ramp limit parameters: If measured frequency is above or below these limits the system will skip the ramp.
  • STORAGE: Added new M-Logic events for when any other battery is charging and any other battery is not "Energy functionality OK" in power management.
  • STORAGE: Added ABB PCS100 ESS protocol.
  • STORAGE: ESS and BB nominal voltages are now selectable as set point to general purpose PID.

Changes

  • STORAGE: Renamed Ningbo BMS to SYL G. S. Air as it relates to the new protocol.
  • STORAGE MARINE/SOLAR MARINE: The auto start/stop signal as digital input or M-Logic is no longer needed for allowing hybrid marine variants to auto start.
  • GENSET: The M-Logic functionality for manual GOV/AVR pulse increase/decrease are now available in the shortcut menu under "Regulation shortcuts" but only works in NoReg mode.
  • GENSET MARINE: The M-Logic functionality for manual GOV/AVR pulse increase/decrease are now available in the shortcut menu under "Regulation shortcuts" for genset marine in PMS but only works in SWBD control.
  • M-Logic: 'Virtual toggle' renamed to 'Virtual event' and 'Virtual switch' renamed to 'Virtual toggle'.
    • Virtual events now works the same on Modbus and in M-Logic. The output of the virtual event will follow the input of the virtual event.
    • Virtual toggles work the same on Modbus and in M-Logic. If the input of the virtual toggle goes high, the output changes state once.
  • STORAGE/SOLAR/DGHYBRID: Updated internal power ramps to be more precise and allow adjustment of internal delay between ramp updates in parameters 2681 and 2682.
  • Added parameter 7075, "Mains Fail Assumption", which enables the Mains controller to assume that the mains have just recovered at start-up, allowing it to run the OK timers.

Corrections

  • GENSET LAND & MARINE: If idle run was active, RMI oil pressure alarms would be active before it was detected that the engine was running. This has been changed so that the engine must be running before the alarms can be active.
  • STORAGE: Fixed issue where the voltage set point does not take voltage transformer into account. Ratio between ESS Nom U (Ch 6004) and BB Nom U (Ch 6053) is now multiplied to take voltage transformer into account when calculating voltage set point to PCS.
  • STORAGE: Oztek OZpcs-rs40 protocol correction: P and Q set points are now sent in both on-grid and off-grid instead of only on-grid.
  • Gen stop and GB Off M-Logic command can now stop the genset during the start sequence.
  • Digital input texts are shown correctly in display menu.
  • GENSET: M-Logic output to change PMS priority selection (#8031) to fuel optimisation was missing.
  • Remote display: Supervision view should now work with a continuous display on the remote unit.
  • ATS: Fixed controller displaying engine symbols at start-up on supervision view page.
  • HYBRID: Empty parameters in display with parameter list setup is no longer shown.
  • EIC: Custom DM1 alarms was not triggered. This has been fixed.
  • Fixed an issue where unsupported application alarm values were incorrect for unsupported Open PMS applications.
  • GENSET MARINE: ISLAND setup with two gensets now automatically starts second genset based on LD start.
  • GENSET MARINE and SHORE: TEST function removed. Still available for EDG.
  • STORAGE: Fixed issue for ESS protocol Sungrow LC200 DPS where charge and discharge capacity scaling was incorrect.
  • STORAGE/STORAGE MARINE: Fixed an issue where controller could continuously start and stop in AUTO mode.
  • GENSET MARINE: GB open without deload corrected.
  • GENSET MARINE: Removed PID1 from shortcut menu when Genset Marine is not a single controller/EDG application.
  • In the USW parameter list, Mains and BTB controllers would show that an inhibit was applied, even though it was not. This has been fixed.
  • STORAGE: Kubank LEMS BCU - Fixed issue where DC current could not be shown as a negative value. Added 3 new measurement values for phase voltages.
  • STORAGE: Updated Nomad BCU protocol - Droop and grid mode logic changed, reading faults and warnings updated to new Modbus addresses and more.
  • STORAGE/SOLAR: Corrected wrong Modbus addresses like Active power in address 40034 to address 33 and other registers for Cummins PC3 x PCC3300 powermeter protocol.
  • GENSET: The frequency/voltage regulation mode is no longer dependent on the frequency detection level when running with the GB closed.
  • GENSET: Show DEF level on all measurement views.
  • STORAGE: SinExcel PWS2 30K and SinExcel 30P ESS protocols have been adjusted to comply with SinExcel Modbus communication requirements.
  • M-Logic virtual toggles (previously named switches) can now be read over Modbus.
  • STORAGE/SOLAR: Fixed an issue where analogue output measurements was not working when measurement origin was set to ESS/PV communication.
  • SOLAR: Fixed an issue where parameter 7553 "RTU broadcast ID" was not accessible in PV communication menu.

1.31.0

05/05/2025

  • USW version required: 3.62.0
  • TDU version required: 1.4.3.1

PM compatibility: 1.41.0

New features

  • STORAGE: Added possibility of remote start over Modbus for DSE 8xxx, 7xxx, 6xxx, 4xxx power meter protocol.
  • STORAGE: Added global/local start of external genset(s) in open PMS.
  • STORAGE: Added possibility of remote start over Modbus for DEIF Genset control power meter protocol.
  • STORAGE: Added Lanli Tech BMS protocol.
  • STORAGE: Added Sicon VSG ESS protocol.
  • EIC: Added many new SPN texts for DM1 log.
  • STORAGE: Added Sungrow LC300 protocol support.
  • EIC: Added support for Scania S6 Industrial.
  • STORAGE: Added SYL Golden Shield Liquid-cooled (SYL G. S. Liq) BMS protocol.
  • STORAGE: Added new parameter 8043 "PMS Isochr. Q ctrl" which enables off-grid reactive power regulation in a PMS Isochronous master setup.
  • STORAGE: Added two new M-Logic outputs for skipping P ramp up and another for P ramp down.
  • STORAGE: Added three new parameters for following or skipping ramps.
    • Isochronous load share parameter: When the controller is isomaster and another storage controller is on the busbar it will no longer skip ramp if iso load share parameter is enabled.
    • Over-frequency and under-frequency ramp limit parameters: If measured frequency is above or below these limits the system will skip the ramp.
  • STORAGE: Added new M-Logic events for when any other battery is charging and any other battery is not "Energy functionality OK" in power management.
  • STORAGE: Added ABB PCS100 ESS protocol.
  • STORAGE: ESS and BB nominal voltages are now selectable as set point to general purpose PID.

Changes

  • STORAGE: Renamed Ningbo BMS to SYL G. S. Air as it relates to the new protocol.
  • STORAGE MARINE/SOLAR MARINE: The auto start/stop signal as digital input or M-Logic is no longer needed for allowing hybrid marine variants to auto start.
  • GENSET: The M-Logic functionality for manual GOV/AVR pulse increase/decrease are now available in the shortcut menu under "Regulation shortcuts" but only works in NoReg mode.
  • GENSET MARINE: The M-Logic functionality for manual GOV/AVR pulse increase/decrease are now available in the shortcut menu under "Regulation shortcuts" for genset marine in PMS but only works in SWBD control.
  • M-Logic: 'Virtual toggle' renamed to 'Virtual event' and 'Virtual switch' renamed to 'Virtual toggle'.
    • Virtual events now works the same on Modbus and in M-Logic. The output of the virtual event will follow the input of the virtual event.
    • Virtual toggles work the same on Modbus and in M-Logic. If the input of the virtual toggle goes high, the output changes state once.
  • STORAGE/SOLAR/DGHYBRID: Updated internal power ramps to be more precise and allow adjustment of internal delay between ramp updates in parameters 2681 and 2682.
  • Added parameter 7075, "Mains Fail Assumption", which enables the Mains controller to assume that the mains have just recovered at start-up, allowing it to run the OK timers.

Corrections

  • GENSET LAND & MARINE: If idle run was active, RMI oil pressure alarms would be active before it was detected that the engine was running. This has been changed so that the engine must be running before the alarms can be active.
  • STORAGE: Fixed issue where the voltage set point does not take voltage transformer into account. Ratio between ESS Nom U (Ch 6004) and BB Nom U (Ch 6053) is now multiplied to take voltage transformer into account when calculating voltage set point to PCS.
  • STORAGE: Oztek OZpcs-rs40 protocol correction: P and Q set points are now sent in both on-grid and off-grid instead of only on-grid.
  • Gen stop and GB Off M-Logic command can now stop the genset during the start sequence.
  • Digital input texts are shown correctly in display menu.
  • GENSET: M-Logic output to change PMS priority selection (#8031) to fuel optimisation was missing.
  • Remote display: Supervision view should now work with a continuous display on the remote unit.
  • ATS: Fixed controller displaying engine symbols at start-up on supervision view page.
  • HYBRID: Empty parameters in display with parameter list setup is no longer shown.
  • EIC: Custom DM1 alarms was not triggered. This has been fixed.
  • Fixed an issue where unsupported application alarm values were incorrect for unsupported Open PMS applications.
  • GENSET MARINE: ISLAND setup with two gensets now automatically starts second genset based on LD start.
  • GENSET MARINE and SHORE: TEST function removed. Still available for EDG.
  • STORAGE: Fixed issue for ESS protocol Sungrow LC200 DPS where charge and discharge capacity scaling was incorrect.
  • STORAGE/STORAGE MARINE: Fixed an issue where controller could continuously start and stop in AUTO mode.
  • GENSET MARINE: GB open without deload corrected.
  • GENSET MARINE: Removed PID1 from shortcut menu when Genset Marine is not a single controller/EDG application.
  • In the USW parameter list, Mains and BTB controllers would show that an inhibit was applied, even though it was not. This has been fixed.
  • STORAGE: Kubank LEMS BCU - Fixed issue where DC current could not be shown as a negative value. Added 3 new measurement values for phase voltages.
  • STORAGE: Updated Nomad BCU protocol - Droop and grid mode logic changed, reading faults and warnings updated to new Modbus addresses and more.
  • STORAGE/SOLAR: Corrected wrong Modbus addresses like Active power in address 40034 to address 33 and other registers for Cummins PC3 x PCC3300 powermeter protocol.
  • GENSET: The frequency/voltage regulation mode is no longer dependent on the frequency detection level when running with the GB closed.
  • GENSET: Show DEF level on all measurement views.
  • STORAGE: SinExcel PWS2 30K and SinExcel 30P ESS protocols have been adjusted to comply with SinExcel Modbus communication requirements.
  • M-Logic virtual toggles (previously named switches) can now be read over Modbus.
  • STORAGE/SOLAR: Fixed an issue where analogue output measurements was not working when measurement origin was set to ESS/PV communication.
  • SOLAR: Fixed an issue where parameter 7553 "RTU broadcast ID" was not accessible in PV communication menu.